Motor circuit breaker, TeSys GV4, 3P, 115A, Icu 50kA, thermal magnetic, Everlink terminals
TeSys GV motor circuit breaker, 3 poles (3P), 115A/690V, for protection of 3-phase motors 37-55kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 65-115A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Product Highlights
- New modern look & feel of all machines
- Wide range of GVs: Magnetic, thermal magnetic, different sizes (GV2,GV3,GV4)
- Easier to install and operate with multi-standard screws
- Safe and long-lasting power connection with EverLink terminals
- Digital customer experience for technical documents
For full spec sheet download please click here or contact our support team.
Quotation for Bulk Orders or Backorders
Need large quantities, custom builds, or project pricing? Request a formal quote and our sales team will get back to you quickly with bulk discounts, lead times, and delivery options. Ideal for contractors, resellers, and tenders.